Installing and using explosion-proof electrical equipment in hazardous and explosive areas is the most basic requirement for safety.

But what issues should be noted when selecting and installing explosion-proof electrical equipment? Below, Zhongnuo Testing will share a few points with everyone.

1、 The selection of explosion-proof electrical equipment should meet the requirements of hazardous areas

(1) Electrical equipment for explosive hazardous environments should be selected based on the hazard level of the installation location, the group and level of hazardous substances, the type and usage conditions of electrical equipment.

(2) The group and level of the selected electrical equipment should not be lower than the group and level of hazardous substances in the environment.

(3) When there are two or more hazardous substances, the one with the higher degree of danger should be selected.

(4) Gas explosion-proof electrical equipment and dust explosion-proof electrical equipment cannot be mixed.

(5) In explosive hazardous environments, portable electrical equipment should be minimized or avoided as much as possible.

(6) Try to install as few pin sockets as possible.

2、 The installation and laying of explosion-proof electrical equipment comply with regulatory requirements

(1) In explosive and fire hazardous environments, the installation location, laying method, wire material, connection method, etc. of electrical equipment circuits should be adapted to the regional hazard level.

(2) Explosion accidents caused by sparks generated by exposed or aged cables should be avoided.

3、 Technical requirements for explosion prevention in hazardous and explosive areas

1. Eliminate or reduce explosive mixtures

(1) Eliminating or reducing explosive mixtures includes adopting enclosed operations to prevent the leakage of explosive mixtures;

(2) Clean up the accumulated dust on site and prevent the accumulation of explosive mixtures;

(3) Design a positive pressure chamber to prevent explosive mixtures from entering areas with ignition sources;

(4) Take open work or ventilation measures to dilute explosive mixtures;

(5) Fill hazardous spaces with inert or inert gases to prevent the formation of explosive mixtures.

2. Isolation

(1) Dangerous equipment should be installed in separate rooms and sealed off on partition walls.

(2) Electric motor partition transmission, lighting fixtures, and glass window lighting are all isolation measures.

3. Eliminate ignition source

(1) Select electrical equipment and design electrical circuits based on the characteristics of explosive hazardous environments and the level and group of hazardous materials.

(2) Ensure the safe operation of electrical equipment and electrical circuits. Safe operation includes current, voltage, temperature rise, and temperature not exceeding the allowable range, including good insulation, good connection and contact, overall integrity, cleanliness, clear markings, etc.

4. Grounding measures

(1) Attention should be paid to grounding in explosive hazardous environments: all uncharged metal objects should be equipotential bonded;

(2) If low voltage is distributed by the grounding system, TN-S system should be used instead of TN-C system;

(3) If the low voltage is distributed by an ungrounded system, an IT system should be used and equipped with protective devices that can automatically cut off the power supply in case of severe leakage or alarm devices that can emit dual signals of sound and light.

4、 Regularly conduct on-site explosion-proof safety inspections of hazardous and explosive areas

According to the AQ 3009-2007 "Explosion proof Specification for Electrical Safety in Hazardous Areas" standard, explosion-proof electrical equipment in use must be entrusted to a testing center with explosion-proof professional qualifications for testing the performance, installation, maintenance, etc. of explosion-proof electrical appliances at least once every 3 years. Any non compliant items must be rectified in a timely manner, and the inspection report and rectification situation must be filed with the safety production supervision and management department.Regular on-site inspections of explosion-proof electrical equipment in use can promptly identify problems in hazardous areas and maximize the containment and elimination of potential accidents. This is not only a requirement from the safety production department, but also an emphasis on the safety of one's own life and property by the enterprise.


Safety is no small matter, and electrical safety in explosive hazardous areas is related to the safety production of enterprises and the country. Pay attention to safety and explosion prevention!



Related Recommendations
Contact us
0755-2102 2109
Add: 13F, Building C, Kangjia Guangming Technology Center, No. 288 Xingxin Road, Guangming District, Shenzhen
Follow us
Copyright: Shenzhen Zhongnuo Testing Technology Co., Ltd. 粵ICP備18004888號
Service Hotline
18924609560
點(diǎn)擊這里給我發(fā)消息 1354407946
點(diǎn)擊這里給我發(fā)消息 1354407946
主站蜘蛛池模板: wwwxxx在线| 成人性生交大片免费看在线播放 | xxxx性公交车上激情xxxxx | 国产一级特黄aa大片免费看 | 日本最新免费二区 | 在线黄色软件 | 久久精品99久久久久久2456 | 国产成人在线网站 | 久久黄色一级视频 | 亚洲欧美视频二区 | 色综合久久久久久久 | 成年人在线观看视频 | 91久久国产露脸精品国产 | 欧美三级一级 | 欧美 日韩 中文字幕 | 91精品一久久香蕉国产线看观看 | 久草成人网 | 国产成人免费网站 | 日韩在线视频免费 | 狠狠爱欧美 | 亚洲一级毛片视频 | 欧美毛片免费看 | 91精品国产99久久久久 | 久久国产一级毛片一区二区 | 国产一区二区视频在线观看免费 | 成年人网站免费在线观看 | 免费一级毛片在线观看 | 一区二区三区伦理片 | 日日碰狠狠躁久久躁 | 911久久香蕉国产线看观看 | 国产视频九九九 | 免费看逼网站 | 99精品视频免费看 | www.色17.com| 色五婷婷| 精品色视频 | 成人免费淫片aa视频免费 | 嫩草视频网站 | 午夜 国产| 久久这里只有精品9 | 一级香蕉视频在线观看 |